Code P10-10104: I1 Overcurr UPos

Issue Description & Safety Warning

The Allen-Bradley PowerFlex 750 Drive has triggered a critical I1 Overcurr UPos alarm. Immediate attention from a qualified operator or maintenance technician is required to prevent secondary damage to the equipment or spoiled parts during the manufacturing cycle. Always ensure standard safety and LOTO procedures are followed before accessing electrical cabinets.

Official Troubleshooting Steps

Type: Resettable Fault Coast Y Y An instantaneous overcurrent (IOC) has occurred in the U, V, or W phase, positive or negative leg. • Reduce the mechanical load. • Check the motor and connections. • With motor disconnected, run the drive in open loop, in V/Hz mode and check for sufficient output phase-to-phase voltages. If an IOC occurs immediately after restarting the drive, check the appropriate current sensor. • Check the power and signal connections to the gate driver board for the phase that is identified, or replace it. The IGBT could also have failed open (and the opposite leg is receiving excess current).

Source: Allen-Bradley PowerFlex 750-Series AC Drives Programming Manual (750-PM001)

Last reviewed: 2026-07-01 · Verified against the manufacturer’s official documentation.

About Allen-Bradley PowerFlex 750 Drive Alarms

Allen-Bradley controllers include extensive self-diagnostics that flag or halt the machine when a fault is detected. Error code P10-10104 on the PowerFlex 750 Drive identifies one specific fault condition — its documented cause and the official corrective steps are listed above, sourced from Allen-Bradley's service documentation. Always confirm against the manual for your exact machine configuration and follow LOTO procedures before servicing.

Complete Alarm List: 663 Allen-Bradley PowerFlex 750 Drive codes.

Have a better solution?

Help the industrial community by sharing your repair experience for code P10-10104.

Manual conversion service

Need a searchable reference for more Allen-Bradley PowerFlex 750 Drive manuals?

We structure equipment manuals into searchable code, title, cause, solution, safety note, and source-reference data. Send a PDF and example searched codes when you need public pages, private search, or structured exports.

Convert PDF fault-code charts and manuals into clean data.
Build public SEO pages or private internal search tools.
Prioritize updates around codes and manuals people search for.
Request manual conversion Email PDFs to manuals.errordb@gmail.com
Advertisement

Space reserved for Google AdSense / Industrial Affiliate Links

Monetization target for 2026

Related Allen-Bradley PowerFlex 750 Drive Codes