Code P11-CONV-11235: C2 Ground Fault
Issue Description & Safety Warning
The Allen-Bradley PowerFlex 750 Drive has triggered a critical C2 Ground Fault alarm. Immediate attention from a qualified operator or maintenance technician is required to prevent secondary damage to the equipment or spoiled parts during the manufacturing cycle. Always ensure standard safety and LOTO procedures are followed before accessing electrical cabinets.
Official Troubleshooting Steps
Safety notice — qualified personnel only
- Electrical: drives and power supplies can hold lethal voltage after power-off (DC-link capacitors). Isolate, lock out, and verify zero energy with a meter before touching terminals.
This page is a reference summary, not a substitute for the OEM manual or your site’s LOTO procedure. FaultResolve accepts no liability for work carried out based on it. See our Terms.
Type: Resettable Fault Coast Y Y The converter input ground current (peak) has exceeded the threshold set P16 [Gnd Cur Flt Lvl] (port 11) for 5 line cycles. A possible internal short in the drive between a phase, ground, or the DC bus can have occurred. • Verify that the current transducer wiring harness is connected to the converter gate firing board and that they are functioning properly. If necessary, replace all three current transducers (CTs). • If the current transducer wiring harness is connected and the CTs are functioning properly, replace the converter gate firing board. • To determine if there is an imbalance between the phases, view the input phase current values in [Cn L1 Phase Curr], [Cn L2 Phase Curr], and [Cn L3 Phase Curr] (port 11). [Cn Gnd Current] (port 11) is the calculated (not measured) ground current based on the phase currents. If necessary, use trending when the ground fault occurs upon drive power-up.
Source: Allen-Bradley PowerFlex 750-Series AC Drives Programming Manual (750-PM001)
Last reviewed: 2026-07-01 · Verified against the manufacturer’s official documentation.
About Allen-Bradley PowerFlex 750 Drive Alarms
Allen-Bradley controllers include extensive self-diagnostics that flag or halt the machine when a fault is detected. Error code P11-CONV-11235 on the PowerFlex 750 Drive identifies one specific fault condition — its documented cause and the official corrective steps are listed above, sourced from Allen-Bradley's service documentation. Always confirm against the manual for your exact machine configuration and follow LOTO procedures before servicing.
Complete Alarm List: 663 Allen-Bradley PowerFlex 750 Drive codes.
Need a searchable reference for more Allen-Bradley PowerFlex 750 Drive manuals?
We structure equipment manuals into searchable code, title, cause, solution, safety note, and source-reference data. Send a PDF and example searched codes when you need public pages, private search, or structured exports.