代碼 F00061: Par Cl. MMC-PS not fitted Fault
問題描述與安全警告
Siemens SINAMICS G120 CU240S Drive 觸發了嚴重的 Par Cl. MMC-PS not fitted Fault 警報。需要由合格的操作員或維修技師立即處理,以防止在製造週期中對設備造成二次損壞或導致零件報廢。在接觸電氣控制箱之前,請務必確保遵循標準安全和停機掛牌 (LOTO) 程序。
官方故障排除步驟
Reaction: OFF 2 Acknowledge: Quit fault eg. via DI2 Cause: MMC-PS Cloning Failed. - r0949 = 0: MMC-PS Not Connected or incorrect MMC-PS Type - r0949 = 1: MMC-PS cannot write to MMC - r0949 = 2: MMC-PS File not available - r0949 = 3: MMC-PS cannot read the file - r0949 = 4: MMC-PS problems in the clone File (e.g CRC) Remedy: - r0949 = 0: Use MMC-PS with FAT12 or FAT16 format or correct MMC-PS Type, or fit an MMC-PS to Drive. - r0949 = 1: Check MMC (e.g is MMC full) - Format MMC again to FAT16 - r0949 = 2: Put the correct named file in the correct directory /USER/SINAMICS/DATA. - r0949 = 3: Make sure File is accesable. Recreate File if possible - r0949 = 4: File has been changed - Recreate File
Source: SINAMICS G120 Control Units CU240S Faults and Alarms (Edition 05/2007)
Last reviewed: 2026-07-01 · Verified against the manufacturer’s official documentation.
關於 Siemens SINAMICS G120 CU240S Drive 警報
由 Siemens 製造的工業控制器具有廣泛的診斷系統,用於保護內部電路和機械連桿。當 SINAMICS G120 CU240S Drive 出現類似 F00061 的錯誤代碼時,通常表示指令值與實際感測器回饋之間存在不匹配。
Have a better solution?
Help the industrial community by sharing your repair experience for code F00061.
Need a searchable reference for more Siemens SINAMICS G120 CU240S Drive manuals?
We structure equipment manuals into searchable code, title, cause, solution, safety note, and source-reference data. Send a PDF and example searched codes when you need public pages, private search, or structured exports.
Space reserved for Google AdSense / Industrial Affiliate Links
Monetization target for 2026