代碼 F00395: Acceptance Test / Confirmation pending
問題描述與安全警告
Siemens SINAMICS G120 CU240S Drive 觸發了嚴重的 Acceptance Test / Confirmation pending 警報。需要由合格的操作員或維修技師立即處理,以防止在製造週期中對設備造成二次損壞或導致零件報廢。在接觸電氣控制箱之前,請務必確保遵循標準安全和停機掛牌 (LOTO) 程序。
官方故障排除步驟
Reaction: OFF 2 Acknowledge: Quit fault eg. via DI2 Cause: This fault occurs after a Powermodul (PM) / Control Unit (CU) Swap or a Startup Clone. It can also be caused by a faulty read from the EEPROM, see F0051 for more details. The parameterset after a CU swap or a startup clone could have changed and might not match the application. This parameterset needs to be checked before the drive can start a motor. - r0949 = 3 / 4: Swap of PM/CU - r0949 = 5: Startup Clone via MMC has been performed - r0949 = 10: Before the last power up an acceptance test was pending due to a swap or a startup clone. Remedy: Safety Units: An Acceptance Test needs to be performed. Follow the the steps of the Acceptance Log which is part of the Oper- ating Instructions. After performing the acceptance test the fault can be acknowledged by the following procedure: P0010 = 30 P9761 = Safety password P7844 = 0 The fault will be cleared automatically and P0010 will be set back to 0 Non Safety Units: The current parameterset needs to be checked and confirmed by clearing the fault or setting P7844 = 0.
Source: SINAMICS G120 Control Units CU240S Faults and Alarms (Edition 05/2007)
Last reviewed: 2026-07-01 · Verified against the manufacturer’s official documentation.
關於 Siemens SINAMICS G120 CU240S Drive 警報
由 Siemens 製造的工業控制器具有廣泛的診斷系統,用於保護內部電路和機械連桿。當 SINAMICS G120 CU240S Drive 出現類似 F00395 的錯誤代碼時,通常表示指令值與實際感測器回饋之間存在不匹配。
Have a better solution?
Help the industrial community by sharing your repair experience for code F00395.
Need a searchable reference for more Siemens SINAMICS G120 CU240S Drive manuals?
We structure equipment manuals into searchable code, title, cause, solution, safety note, and source-reference data. Send a PDF and example searched codes when you need public pages, private search, or structured exports.