Code 2001: PLC has not started up
Issue Description & Safety Warning
The Siemens SINUMERIK 840D CNC has triggered a critical PLC has not started up alarm. Immediate attention from a qualified operator or maintenance technician is required to prevent secondary damage to the equipment or spoiled parts during the manufacturing cycle. Always ensure standard safety and LOTO procedures are followed before accessing electrical cabinets.
Official Troubleshooting Steps
Root Cause: During control boot-up, the integrated PLC did not deliver its first cyclic heartbeat to the NCK before the startup watchdog timer expired (`MD10120 $MN_PLC_RUNNINGUP_TIMEOUT`, factory default 1.0 s). Troubleshooting Steps: 1. Observe the NCU front panel LEDs immediately after power-on: check whether the 7-segment display reaches `6` (NCK ready) while the PLC `PS` (STOP) LED stays lit or flashes. 2. Verify the NCU PLC mode rotary switch (`S4` on NCU 7xx, `S4` on NCU 57x) was not accidentally left in position `2` (STOP) after maintenance service—position `0` is required for normal PLC `RUN`. 3. Connect STEP 7 to inspect the PLC Diagnostic Buffer for startup OB100 failures, corrupted retentive DB memory after a dead NCU backup battery/supercap, or hardware configuration mismatches on PROFIBUS/PROFINET. 4. If a cold boot lost volatile S7 program memory (Powerline battery fault), reload the verified `PLC.ARC` series startup archive via HMI Startup -> Series Start-up.
Source: SINUMERIK 840D sl / 840Di sl / SINAMICS S120 Diagnostics Manual (DAsl, 03/2009)
Last reviewed: 2026-11-27 · Verified against the manufacturer’s official documentation.
Field Experience, Common Misdiagnoses & Applicable Models
Source: FaultResolve Field Engineering Notes · Ref: Siemens SINUMERIK 840D sl / Powerline Diagnostics Manual
Field Experience: Alarm 2001 appearing right after a long holiday power-down on older SINUMERIK 840D Powerline machines is the classic signature of an exhausted 3 V lithium backup battery in the NCU fan/battery cassette (6FC5247-0AA06-0AA0): SRAM wiped clean while powered off, leaving the PLC empty in STOP so only NC.ARC and PLC.ARC reload will revive the machine. On newer 840D sl (NCU 710/720/730, battery-free CF card architecture), Alarm 2001 after maintenance is far more often a technician leaving rotary switch S4 at 1 or 2, or heavy OB100 initialization waiting on slow third-party PROFINET slaves exceeding MD10120.
Common Misdiagnoses: Replacing the NCU card for "dead PLC" when rotary switch S4 behind the NCU flap was bumped off 0, or reloading PLC.ARC without reloading matching NC.ARC after total SRAM loss on 840D Powerline—leaving tool management tables out of sync with DB blocks and causing tool-changer crashes.
Applicable Models & Manual Editions: Covers SINUMERIK 840D Powerline (NCU 571–573), 810D, and SINUMERIK 840D sl / 840Di sl (NCU 710.2/720.2/730.2/7x0.3 PN). Referenced in Diagnostics Manual (DAsl, 03/2009 & 01/2015).
About Siemens SINUMERIK 840D CNC Alarms
Siemens controllers include extensive self-diagnostics that flag or halt the machine when a fault is detected. Error code 2001 on the SINUMERIK 840D CNC identifies one specific fault condition — its documented cause and the official corrective steps are listed above, sourced from Siemens's service documentation. Always confirm against the manual for your exact machine configuration and follow LOTO procedures before servicing.
Complete Alarm List: 4014 Siemens SINUMERIK 840D CNC codes.
Need a searchable reference for more Siemens SINUMERIK 840D CNC manuals?
We structure equipment manuals into searchable code, title, cause, solution, safety note, and source-reference data. Send a PDF and example searched codes when you need public pages, private search, or structured exports.