代碼 oPE15: rque Control Setting Error
問題描述與安全警告
Yaskawa A1000 AC Drive 觸發了嚴重的 rque Control Setting Error 警報。需要由合格的操作員或維修技師立即處理,以防止在製造週期中對設備造成二次損壞或導致零件報廢。在接觸電氣控制箱之前,請務必確保遵循標準安全和停機掛牌 (LOTO) 程序。
官方故障排除步驟
Code type: Operator programming error Manual section: Yaskawa A1000 Troubleshooting Torque Control in enabled (d5-01 = 1) while the Speed/Torque Control switch function is assigned to a digital input (H1-□□ = 71). Correct the parameter settings. Either Torque Control is enabled by d5-01 = 1, the or Speed/Torque Control switch is assigned to a digital input H1-□□ = 71, while at the same time: - Feed Forward is enabled (n5-01 = 1), or - Droop Control is enabled (b7-01 ≠ 0), or - Intelligent Stall Prevention or Intelligent Stall Prevention 2 is enabled (L3-04 = 2 or 5), or - A digital input is set for the power KEB 1 or KEB 2 (H1-□□ = 7A or 7B)
Source: Yaskawa AC Drive A1000 High Performance Vector Control Drive Technical Manual (SIEP C710616 21H)
Last reviewed: 2026-07-01 · Verified against the manufacturer’s official documentation.
關於 Yaskawa A1000 AC Drive 警報
由 Yaskawa 製造的工業控制器具有廣泛的診斷系統,用於保護內部電路和機械連桿。當 A1000 AC Drive 出現類似 oPE15 的錯誤代碼時,通常表示指令值與實際感測器回饋之間存在不匹配。
完整警報清單: 280 Yaskawa A1000 AC Drive 代碼s.
Have a better solution?
Help the industrial community by sharing your repair experience for code oPE15.
Need a searchable reference for more Yaskawa A1000 AC Drive manuals?
We structure equipment manuals into searchable code, title, cause, solution, safety note, and source-reference data. Send a PDF and example searched codes when you need public pages, private search, or structured exports.