代码 Uv: Undervoltage
问题描述与安全警告
Yaskawa A1000 AC Drive 触发了严重的 Undervoltage 警报。需要由合格的操作员或维修技师立即处理,以防止在制造周期中对设备造成二次损坏或导致零件报废。在接触电气控制箱之前,请务必确保遵循标准安全和停机挂牌 (LOTO) 程序。
官方故障排除步骤
Code type: Alarm / minor fault Manual section: Yaskawa A1000 Troubleshooting Phase loss in the drive input power. Check for wiring errors in the main circuit drive input power. Correct the wiring. Loose wiring in the drive input power terminals. - Ensure the terminals have been properly tightened. - Apply the tightening torque to the terminals as specified. Refer to Wire Gauges and Tightening Torque on page 76 There is a problem with the drive input power voltage. - Check the voltage. - Lower the voltage of the drive input power so that it is within the limits listed in the specifications. Drive internal circuitry is worn. - Check the maintenance time for the capacitors (U4-05). - Replace either the control board or the entire drive if U4-05 exceeds 90%. For instructions on replacing the control board, contact Yaskawa or your nearest sales representative. The drive input power transformer is too small and voltage drops when the power is switched on. - Check for an alarm when the magnetic contactor, line breaker, and leakage breaker are closed. - Check the capacity of the drive input power transformer. Air inside the drive is too hot. Check the temperature inside the drive. The CHARGE light is broken or disconnected. Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest sales representative.
Source: Yaskawa AC Drive A1000 High Performance Vector Control Drive Technical Manual (SIEP C710616 21H)
Last reviewed: 2026-07-01 · Verified against the manufacturer’s official documentation.
关于 Yaskawa A1000 AC Drive 警报
由 Yaskawa 制造的工业控制器具有广泛的诊断系统,用于保护内部电路和机械连杆。当 A1000 AC Drive 出现类似 Uv 的错误代码时,通常表示指令值与实际传感器反馈之间存在不匹配。
完整报警清单: 280 Yaskawa A1000 AC Drive 代码s.
Have a better solution?
Help the industrial community by sharing your repair experience for code Uv.
Need a searchable reference for more Yaskawa A1000 AC Drive manuals?
We structure equipment manuals into searchable code, title, cause, solution, safety note, and source-reference data. Send a PDF and example searched codes when you need public pages, private search, or structured exports.
Space reserved for Google AdSense / Industrial Affiliate Links
Monetization target for 2026