Code PF (Fault): Input Phase Loss
Issue Description & Safety Warning
The Yaskawa V1000 AC Drive has triggered a critical Input Phase Loss alarm. Immediate attention from a qualified operator or maintenance technician is required to prevent secondary damage to the equipment or spoiled parts during the manufacturing cycle. Always ensure standard safety and LOTO procedures are followed before accessing electrical cabinets.
Official Troubleshooting Steps
Code type: Fault Manual section: Yaskawa V1000 Troubleshooting There is phase loss in the drive input power. - Check for wiring errors in the main circuit drive input power. - Correct the wiring. There is loose wiring in the drive input power terminals. - Ensure the terminals are tightened properly. - Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Gauges and Tightening Torques on page 56 for details. There is excessive fluctuation in the drive input power voltage. - Check the voltage from the drive input power. - Review the possible solutions for stabilizing the drive input power. - Disable Input Phase Loss Detection (L8-05 = “0”). PF is detected if DC bus ripple is too high. If it is disabled, there is no fault but the ripple is still too high, thereby the capacitors are stressed more and lose lifetime. There is poor balance between voltage phases. - Stabilize drive input power or disable phase loss detection.
Source: Yaskawa AC Drive V1000 Compact Vector Control Drive Technical Manual (SIEP C710606 19D)
Last reviewed: 2026-07-01 · Verified against the manufacturer’s official documentation.
About Yaskawa V1000 AC Drive Alarms
Yaskawa controllers include extensive self-diagnostics that flag or halt the machine when a fault is detected. Error code PF (Fault) on the V1000 AC Drive identifies one specific fault condition — its documented cause and the official corrective steps are listed above, sourced from Yaskawa's service documentation. Always confirm against the manual for your exact machine configuration and follow LOTO procedures before servicing.
Complete Alarm List: 153 Yaskawa V1000 AC Drive codes.
Have a better solution?
Help the industrial community by sharing your repair experience for code PF (Fault).
Need a searchable reference for more Yaskawa V1000 AC Drive manuals?
We structure equipment manuals into searchable code, title, cause, solution, safety note, and source-reference data. Send a PDF and example searched codes when you need public pages, private search, or structured exports.