代码 F00041: Motor Data Identification Failure

问题描述与安全警告

Siemens SINAMICS G120 CU240S Drive 触发了严重的 Motor Data Identification Failure 警报。需要由合格的操作员或维修技师立即处理,以防止在制造周期中对设备造成二次损坏或导致零件报废。在接触电气控制箱之前,请务必确保遵循标准安全和停机挂牌 (LOTO) 程序。

官方故障排除步骤

Reaction: OFF 2 Acknowledge: Quit fault eg. via DI2 Cause: Motor data identification failed. - r0949 = 0: Load missing - r0949 = 1: Current limit level reached during identification. - r0949 = 2: Identified stator resistance less than 0.1% or greater than 100%. - r0949 = 3: Identified rotor resistance less than 0.1% or greater than 100%. - r0949 = 4: Identified stator reactance less than 50% and greater than 500% - r0949 = 5: Identified main reactance less than 50% and greater than 500% - r0949 = 6: Identified rotor time constant less than 10ms or greater than 5s - r0949 = 7: Identified total leakage reactance less than 5% and greater than 50% - r0949 = 20: Identified IGBT on-voltage less than 0.5 V or greater than 10 V - r0949 = 30: Current controller at voltage limit - r0949 = 40: Inconsistence of identified dataset, at least one identification failed - r0949 = 41: Writing of calculated magnetizing current P0320 failed - r0949 = 42: Writing of identified stator resistance failed - r0949 = 43: Writing of identified rotor resistance P0354 failed - r0949 = 44: Writing of identified rotor time constant P0622 failed - r0949 = 45: Writing of identified mutual reactance P0360 failed - r0949 = 46: Writing of identified stator leakage reactance P0356 failed - r0949 = 47: Writing of identified rotor leakage reactance P0358 failed - r0949 = 48: Writing of identified on voltage P1825 failed. - r0949 = 49: Writing of the identified dead time compensation P1828 failed Percentage values based on the impedance Zb = Vmot,nom / sqrt(3) / Imot,nom Remedy: Check the following: - r0949 = 0: is the motor connected to the inverter. - r0949 = 1-49: are the motor data in p0304 - p0311 correct. - Check what type of motor wiring is required (star, delta).

Source: SINAMICS G120 Control Units CU240S Faults and Alarms (Edition 05/2007)

Last reviewed: 2026-07-01 · Verified against the manufacturer’s official documentation.

关于 Siemens SINAMICS G120 CU240S Drive 警报

由 Siemens 制造的工业控制器具有广泛的诊断系统,用于保护内部电路和机械连杆。当 SINAMICS G120 CU240S Drive 出现类似 F00041 的错误代码时,通常表示指令值与实际传感器反馈之间存在不匹配。

完整报警清单: 108 Siemens SINAMICS G120 CU240S Drive 代码s.

Have a better solution?

Help the industrial community by sharing your repair experience for code F00041.

Manual conversion service

Need a searchable reference for more Siemens SINAMICS G120 CU240S Drive manuals?

We structure equipment manuals into searchable code, title, cause, solution, safety note, and source-reference data. Send a PDF and example searched codes when you need public pages, private search, or structured exports.

Convert PDF fault-code charts and manuals into clean data.
Build public SEO pages or private internal search tools.
Prioritize updates around codes and manuals people search for.
Request manual conversion Email PDFs to manuals.errordb@gmail.com
Advertisement

Space reserved for Google AdSense / Industrial Affiliate Links

Monetization target for 2026

相关的 Siemens SINAMICS G120 CU240S Drive 代码