Code F00001: Overcurrent
Issue Description & Safety Warning
The Siemens SINAMICS G120 CU240S Drive has triggered a critical Overcurrent alarm. Immediate attention from a qualified operator or maintenance technician is required to prevent secondary damage to the equipment or spoiled parts during the manufacturing cycle. Always ensure standard safety and LOTO procedures are followed before accessing electrical cabinets.
Official Troubleshooting Steps
Safety notice — qualified personnel only
- Electrical: drives and power supplies can hold lethal voltage after power-off (DC-link capacitors). Isolate, lock out, and verify zero energy with a meter before touching terminals.
This page is a reference summary, not a substitute for the OEM manual or your site’s LOTO procedure. FaultResolve accepts no liability for work carried out based on it. See our Terms.
Root Cause: Instantaneous inverter output phase current exceeded the Power Module overcurrent trip threshold (`Reaction: OFF2` coast-to-stop), caused by a motor/cable phase-to-phase or earth short, locked rotor, or severe V/f / vector parameter mismatch. Troubleshooting Steps: 1. Read diagnostic fault value `r0949` via BOP/IOP or STARTER/Startdrive (`r0949 = 0`: hardware IGBT desaturation trip; `r0949 = 1`: software peak current limit). 2. Lock out drive power, wait 5 minutes for DC link discharge, **disconnect the U2/V2/W2 motor cable from the Power Module**, and attempt a brief low-speed jog command with no motor attached: if F00001 STILL trips immediately with open output terminals, the Power Module IGBT bridge is shorted internally and must be replaced. 3. Megger-test the disconnected motor cable and motor windings at 500 VDC to ground (`> 10 MΩ` expected) and check phase-to-phase winding balance with a milliohmmeter. 4. If cabling and motor test clean and the shaft turns freely by hand, verify nameplate motor parameters (`p0304–p0311` vs. `r0206`), increase ramp-up time (`p1120`), reduce starting voltage boost (`p1312`), and run stationary motor ID (`p1900 = 2`).
Source: SINAMICS G120 Control Units CU240S Faults and Alarms (Edition 05/2007)
Last reviewed: 2026-11-27 · Verified against the manufacturer’s official documentation.
Field Experience, Common Misdiagnoses & Applicable Models
Source: FaultResolve Field Engineering Notes · Ref: Siemens SINAMICS G120 CU240S / CU240E-2 List Manual
Field Experience: The single fastest diagnostic split on SINAMICS G120 F00001 is lifting the U2 / V2 / W2 motor leads off the PM240 terminal block! On washdown conveyors, coolant pumps, and rooftop exhaust fans, moisture inside the motor Peckerhead / terminal box or an electromechanical output contactor opening/closing downstream of an active VFD while modulated pulses are enabled causes phase arcing and instant r0949 = 0 hardware trips. Also watch excessive shielded motor cable lengths (> 50 m shielded on frame sizes FSA–FSC without an output reactor)—high cable capacitance charging spikes at PWM edge switching trigger F00001 at the exact millisecond ON/OFF1 is commanded!
Common Misdiagnoses: Repeatedly cycling power and hitting Fault Reset (DI2 / Fn key) on a r0949 = 0 short circuit without meggering the motor leads—five consecutive resets into a bolted ground/phase short will blow a previously intact PM240 IGBT stack! Also note clinicians swapping only the snap-on CU240S Control Unit when IGBT hardware lives in the rear PM240 Power Module.
Applicable Models & Manual Editions: Applies specifically to SINAMICS G120 with CU240S / CU240B (FW V3.x, 5-digit F00001 format, Faults and Alarms Edition 05/2007) and maps conceptually to F30001 / F07801 on newer modular CU240B-2 / CU240E-2 (FW V4.4–V4.7, List Manual LH11) with PM240 / PM240-2 Power Modules.
About Siemens SINAMICS G120 CU240S Drive Alarms
Siemens controllers include extensive self-diagnostics that flag or halt the machine when a fault is detected. Error code F00001 on the SINAMICS G120 CU240S Drive identifies one specific fault condition — its documented cause and the official corrective steps are listed above, sourced from Siemens's service documentation. Always confirm against the manual for your exact machine configuration and follow LOTO procedures before servicing.
Complete Alarm List: 108 Siemens SINAMICS G120 CU240S Drive codes.
Need a searchable reference for more Siemens SINAMICS G120 CU240S Drive manuals?
We structure equipment manuals into searchable code, title, cause, solution, safety note, and source-reference data. Send a PDF and example searched codes when you need public pages, private search, or structured exports.