Code F00002: Overvoltage

Issue Description & Safety Warning

The Siemens SINAMICS G120 CU240S Drive has triggered a critical Overvoltage alarm. Immediate attention from a qualified operator or maintenance technician is required to prevent secondary damage to the equipment or spoiled parts during the manufacturing cycle. Always ensure standard safety and LOTO procedures are followed before accessing electrical cabinets.

Official Troubleshooting Steps

Safety notice — qualified personnel only

  • Electrical: drives and power supplies can hold lethal voltage after power-off (DC-link capacitors). Isolate, lock out, and verify zero energy with a meter before touching terminals.

This page is a reference summary, not a substitute for the OEM manual or your site’s LOTO procedure. FaultResolve accepts no liability for work carried out based on it. See our Terms.

Root Cause: DC link bus voltage (`r0026`) rose above the Power Module hardware overvoltage trip threshold (`~820 VDC` on 400/480 V units; `Reaction: OFF2`), driven either by regenerative motor braking energy or excessive AC mains line surges. Troubleshooting Steps: 1. Check `r0026` (live DC link voltage) at idle and compare incoming 3-phase AC supply against parameter `p0210` (Device Supply Voltage)—a 480 VAC plant line should have `p0210 = 480 V`, not default European `400 V`. 2. Determine WHEN F00002 trips: if it trips **during deceleration or stopping**, high load inertia (fans, centrifuges, flywheels, lowering hoists) is pumping regenerative energy back into the DC link capacitors faster than losses dissipate it. 3. Verify the $V_{dc\_max}$ controller is enabled (`p1240 = 1` when NO external braking resistor is fitted—automatically extending ramp-down time to prevent tripping) and lengthen ramp-down time (`p1121`). 4. If fast controlled stopping is required with an external braking resistor connected to `DCP / R1-R2` on PM240, set `p1240 = 0` (so $V_{dc\_max}$ does not fight the braking chopper!), set braking duty `p1237`, and ohm-check the resistor.

Source: SINAMICS G120 Control Units CU240S Faults and Alarms (Edition 05/2007)

Last reviewed: 2026-11-27 · Verified against the manufacturer’s official documentation.

Expert Guidance

Field Experience, Common Misdiagnoses & Applicable Models

Source: FaultResolve Field Engineering Notes · Ref: Siemens SINAMICS G120 CU240S / CU240E-2 List Manual

Field Experience: Classic parameter trap on SINAMICS G120: when retrofitting an external dynamic braking resistor onto a PM240 (R1 / R2 terminals), leaving p1240 = 1 ($V_{dc_max}$ controller enabled) causes the drive software to stretch deceleration frequency upward right around the chopper firing voltage so the braking resistor barely works or hunts wildly—conversely, disabling p1240 = 0 on a drive that has no braking resistor guarantees instant F00002 on every quick stop! If F00002 trips while sitting idle or at constant speed, look instead at upstream power-factor-correction capacitor banks switching on the plant 480 V transformer and spiking line voltage above 528 VAC.

Common Misdiagnoses: Confusing regenerative PM250 Power Modules (which feed braking energy directly back into the AC mains without resistors, incapable of using braking resistors) with standard PM240 Power Modules! Also check r0949 (0 = hardware comparator spike vs. 1/2 = software $V_{dc}$ threshold).

Applicable Models & Manual Editions: Covers SINAMICS G120 CU240S / CU240B (FW V3.x, CU240S Faults and Alarms Edition 05/2007, 5-digit F00002) and corresponds to F30002 / F07400 on CU240E-2 / CU250S-2 (FW V4.x List Manual LH11).

About Siemens SINAMICS G120 CU240S Drive Alarms

Siemens controllers include extensive self-diagnostics that flag or halt the machine when a fault is detected. Error code F00002 on the SINAMICS G120 CU240S Drive identifies one specific fault condition — its documented cause and the official corrective steps are listed above, sourced from Siemens's service documentation. Always confirm against the manual for your exact machine configuration and follow LOTO procedures before servicing.

Complete Alarm List: 108 Siemens SINAMICS G120 CU240S Drive codes.

Manual conversion service

Need a searchable reference for more Siemens SINAMICS G120 CU240S Drive manuals?

We structure equipment manuals into searchable code, title, cause, solution, safety note, and source-reference data. Send a PDF and example searched codes when you need public pages, private search, or structured exports.