Code F00004: Inverter Over Temperature

Issue Description & Safety Warning

The Siemens SINAMICS G120 CU240S Drive has triggered a critical Inverter Over Temperature alarm. Immediate attention from a qualified operator or maintenance technician is required to prevent secondary damage to the equipment or spoiled parts during the manufacturing cycle. Always ensure standard safety and LOTO procedures are followed before accessing electrical cabinets.

Official Troubleshooting Steps

Safety notice — qualified personnel only

  • Electrical: drives and power supplies can hold lethal voltage after power-off (DC-link capacitors). Isolate, lock out, and verify zero energy with a meter before touching terminals.

This page is a reference summary, not a substitute for the OEM manual or your site’s LOTO procedure. FaultResolve accepts no liability for work carried out based on it. See our Terms.

Root Cause: Measured Power Module heatsink or internal ambient temperature (`r0037`) exceeded the inverter thermal shutdown limit (`Reaction: OFF2`), indicating blocked heatsink cooling, failed cooling fans, high cabinet ambient (`> 40–50 °C`), or excessive PWM switching frequency. Troubleshooting Steps: 1. Check `r0037` (inverter heatsink/chip temperatures) on the BOP/STARTER and verify whether the bottom/top cooling fan(s) on the PM240 Power Module spin up briskly whenever motor pulses are enabled. 2. Blow compressed air (with power off) backward through the external aluminum heatsink fins behind the Power Module—cotton lint, cardboard dust, flour, or machining oil mist frequently packs the fin channels solid while the front plastic cover looks spotless! 3. Check cabinet cooling fans/filters and verify vertical mounting clearances (`>= 100 mm` clear space above and below the PM240 frame). 4. Check PWM pulse frequency (`p1800`): raising `p1800` from the `4 kHz` default to `8–16 kHz` to quiet motor whine severely derates continuous output current (often by 30–50%!) and rapidly overheats the IGBT heatsink.

Source: SINAMICS G120 Control Units CU240S Faults and Alarms (Edition 05/2007)

Last reviewed: 2026-11-27 · Verified against the manufacturer’s official documentation.

Expert Guidance

Field Experience, Common Misdiagnoses & Applicable Models

Source: FaultResolve Field Engineering Notes · Ref: Siemens SINAMICS G120 CU240S / CU240E-2 List Manual

Field Experience: Power Module heatsink fans on SINAMICS G120 (PM240 / PM240-2) are demand-controlled—they intentionally turn OFF at idle, so don't judge the fan until you give a brief RUN command or check fan wear hours! On PM240 frames FSA through FSF, the snap-in fan cartridge at the bottom/top of the Power Module is a standard wear item (~30,000–40,000 operating hours) replaceable in 2 minutes without unbolting the drive from the backplate. Another sneaky trigger occurs when someone mounts two G120 drives directly one above the other without a baffle plate, pumping 65 °C exhaust air from the lower drive straight into the intake of the upper drive!

Common Misdiagnoses: Replacing the entire PM240 Power Module for F00004 when only a $45 snap-in fan kit (6SL3200-0SFxx) stalled, OR overlooking that an acoustic-minded technician raised p1800 pulse frequency to 12 kHz without checking Siemens current-derating curves in the Hardware Installation Manual.

Applicable Models & Manual Editions: Covers SINAMICS G120 CU240S / CU240B (FW V3.x, CU240S Faults and Alarms Edition 05/2007) and maps to F30004 (Heatsink Overtemperature) on CU240E-2 / PM240-2 (FW V4.x List Manual LH11).

About Siemens SINAMICS G120 CU240S Drive Alarms

Siemens controllers include extensive self-diagnostics that flag or halt the machine when a fault is detected. Error code F00004 on the SINAMICS G120 CU240S Drive identifies one specific fault condition — its documented cause and the official corrective steps are listed above, sourced from Siemens's service documentation. Always confirm against the manual for your exact machine configuration and follow LOTO procedures before servicing.

Complete Alarm List: 108 Siemens SINAMICS G120 CU240S Drive codes.

Manual conversion service

Need a searchable reference for more Siemens SINAMICS G120 CU240S Drive manuals?

We structure equipment manuals into searchable code, title, cause, solution, safety note, and source-reference data. Send a PDF and example searched codes when you need public pages, private search, or structured exports.

Convert PDF fault-code charts and manuals into clean data.
Build public SEO pages or private internal search tools.
Prioritize updates around codes and manuals people search for.
Request manual conversion Email PDFs to manuals.errordb@gmail.com

Related Siemens SINAMICS G120 CU240S Drive Codes