Code F00003: Undervoltage

Issue Description & Safety Warning

The Siemens SINAMICS G120 CU240S Drive has triggered a critical Undervoltage alarm. Immediate attention from a qualified operator or maintenance technician is required to prevent secondary damage to the equipment or spoiled parts during the manufacturing cycle. Always ensure standard safety and LOTO procedures are followed before accessing electrical cabinets.

Official Troubleshooting Steps

Safety notice — qualified personnel only

  • Electrical: drives and power supplies can hold lethal voltage after power-off (DC-link capacitors). Isolate, lock out, and verify zero energy with a meter before touching terminals.

This page is a reference summary, not a substitute for the OEM manual or your site’s LOTO procedure. FaultResolve accepts no liability for work carried out based on it. See our Terms.

Root Cause: DC link bus voltage (`r0026`) dropped below the minimum operational undervoltage trip threshold (`Reaction: OFF2`) while the inverter was enabled, due to an AC mains dip/outage, dropped input phase under load, or misconfigured line supply parameter `p0210`. Troubleshooting Steps: 1. Measure all three incoming AC line phases (`L1 / L2 / L3`) under load at the Power Module input terminals—a single blown upstream fuse or pitted input contactor pole lets the drive sit quietly at idle on two phases, then collapses DC bus ripple under load into F00003 (or F00020/F00025). 2. Check parameter `p0210` (Device Supply Voltage) against actual measured plant voltage—if `p0210` was accidentally set to `480 V` on a `380–400 V` supply, the calculated undervoltage threshold sits artificially high and trips on minor sags! 3. Compare live `r0026` DC link voltage on the BOP (`r0026` should read approximately $1.35 \times V_{AC\_line}$, e.g., `~540 VDC` on 400 VAC or `~650 VDC` on 480 VAC) against a calibrated true-RMS meter to verify internal voltage-sensing accuracy. 4. For brief utility grid brownouts on non-hazardous fans/pumps, configure Kinetic Buffering ($V_{dc\_min}$ control in `p1240 = 2 / 3`) or Automatic Restart (`p1210`) where safety standards allow.

Source: SINAMICS G120 Control Units CU240S Faults and Alarms (Edition 05/2007)

Last reviewed: 2026-11-27 · Verified against the manufacturer’s official documentation.

Expert Guidance

Field Experience, Common Misdiagnoses & Applicable Models

Source: FaultResolve Field Engineering Notes · Ref: Siemens SINAMICS G120 CU240S / CU240E-2 List Manual

Field Experience: Whenever a G120 throws F00003 specifically at the moment a heavy motor accelerates while neighboring machines stay online, grab a thermal camera or meter and check the upstream disconnect switch, fuse clips, and safety line contactor (K1) feeding L1/L2/L3! High contact resistance (5–20 ohms across carbonized contactor tips) allows full unloaded voltage (540–650 VDC in r0026) while parked, then drops 150+ volts the instant charging/acceleration current flows! On older high-hour PM240 modules (7+ years in hot cabinets), dried-out electrolytic DC bus capacitors or a failed internal pre-charge relay (charging resistor overheating and opening) also triggers immediate F00003 as soon as load torque builds.

Common Misdiagnoses: Blaming utility power company sags when only ONE VFD out of ten on the same MCC busbar keeps tripping F00003—if sister drives on the same bus don't flinch, your problem is local to that bucket's fuses, contactor, loose L1/L2/L3 lugs, or failing PM240 pre-charge circuit!

Applicable Models & Manual Editions: Applies to SINAMICS G120 CU240S / CU240B (FW V3.x, Edition 05/2007) and corresponds to F30003 on SINAMICS G120 CU240E-2 / PM240-2 (FW V4.x List Manual LH11).

About Siemens SINAMICS G120 CU240S Drive Alarms

Siemens controllers include extensive self-diagnostics that flag or halt the machine when a fault is detected. Error code F00003 on the SINAMICS G120 CU240S Drive identifies one specific fault condition — its documented cause and the official corrective steps are listed above, sourced from Siemens's service documentation. Always confirm against the manual for your exact machine configuration and follow LOTO procedures before servicing.

Complete Alarm List: 108 Siemens SINAMICS G120 CU240S Drive codes.

Manual conversion service

Need a searchable reference for more Siemens SINAMICS G120 CU240S Drive manuals?

We structure equipment manuals into searchable code, title, cause, solution, safety note, and source-reference data. Send a PDF and example searched codes when you need public pages, private search, or structured exports.

Convert PDF fault-code charts and manuals into clean data.
Build public SEO pages or private internal search tools.
Prioritize updates around codes and manuals people search for.
Request manual conversion Email PDFs to manuals.errordb@gmail.com

Related Siemens SINAMICS G120 CU240S Drive Codes